How to install Underfloor Heating in a single area

Two loops in a room

When installing underfloor heating in any room, please be aware that the maximum length of pipe in one loop is 120 linear metres.

Our single area packs come with a minimum of two loops.

For underfloor heating packs larger than 24sqm at 200mm centres, you will need to install two equal loops.

Install approximately 3 to 4 runs (depending on room size) of fixing rail use the insulation clips for the turns and in-between the fixing rails.

One loop in a room

Our single packs up to 24sqm at 200mm centres, can be installed as a single loop.

Install approximately 3 to 4 runs (depending on room size) of fixing rail, using the insulation clips for the turns and in-between the fixing rails.